Idea™ iXP- Transformer Protection System

The iXP-420 is a full-featured relay suitable for a variety of protection applications especially for two-winding transformer protection, monitoring, and monitoring and control.

Highlights

  • Add new functions and features using IDEA Workbench™ Custom Modules
  • Selectable transformer winding configuration
  • Multi-feeder frequency load shedding and restoration logic
  • Selective tripping of both high and low side breakers
  • Breaker health monitoring for both controlled breakers
  • Virtual Test Set™ event record simulator
  • Relay Replay™: The "what-if" analysis tool

Protection Features

  • Two levels of over-excitation (V/Hz) protection (24)
  • Under- and over-voltage (27/59)
  • Fuse-fail detection (27FF)
  • Phase overcurrent (50/51) for each winding
  • Residual overcurrent for each winding (50R/51R)
  • Ground overcurrent with separate CT input for low side winding (50N/51N)
  • Negative-sequence overcurrent (50Q/51Q) for each winding
  • Breaker fail-to-trip and fail-to close for both breakers
  • Sequence overvoltage (59P, 59Q, 59N) and positive sequence undervoltage (27P)
  • Multiple-Step over/under frequency elements with voltage and current supervision (81)
  • Differential protection element (87-1) with dual slope bias characteristic and adjustable knee-point
  • High set differential element (87-2) for fast response to large magnitude internal faults
  • Adjustable 2nd and 5th harmonic restraint on the main differential element
  • Restricted earth fault (87N).Two levels of over-excitation (V/Hz) protection (24)
  • Catalog Section 165-420  