home | about Cooper Power Systems | C3 - Distributor Log In | Cooper Industries | contact us

    Loadbreak Feedthru Inserts

    Feedthru

    (100 K)

    Feedthru

    (93 K)

    The Loadbreak Feedthru Insert
    That's Taken a Turn for the Better

    No More Broken Bushing Well Studs!
    No More Loose Connections!

    Bulletin 91038 (November 1991)

    You don't have to worry any more about installing feedthru inserts into your padmount gear. Cooper Power Systems has made installation easy and trouble free. We have re-designed our feedthru inserts with your concerns in mind. Our new design eliminates the problems heard most when talking to your line personnel.

    "We keep breaking bushing well studs when tightening feedthru inserts."

    "We can never tell when the device is properly seated in the bushing well and worry about loose connections."

    "We are concerned that mechanical wear from repeated installations will degrade the load current carrying capability."

    Cutaway Detail

    Eliminate Broken Bushing Well Studs
    We have incorporated a patented (U.S. Patent No. 5.041.004), ratchet style base and cam stem internal to the "rotatable" feedthru inserts (see cutaway detail).

    When the feedthru insert is installed, this ratchet base is torque actuated to release when the cam stem bottoms on the shoulder of the mating bushing well stud. The ratchet is calibrated to release at between 7 and 14 foot-pounds. This torque range is well below the break point of a bushing well stud, but proven to provide an electrical connection for full for full 200 amp current loading (verified from tests in accordance with ANSI/IEEE 386).

    56 K

    Eliminate Loose Connections
    Once the correct installation torque has been achieved and the ratchet device releases, an audible clicking of the ratchet device indicates to the installer that proper seating has been accomplished. The ratchet device provides 10° incremental positioning in the clockwise direction. A stainless steel bracket is provided to fix the device in the desired position. Final positioning can be accomplished with continued clockwise rotation without compromising the connection made during initial installation. Other feedthru inserts may require counterclockwise positioning that invites the opportunity for a loose connection. Our rotatable feedthru inserts take the worry out!

    All copper (copper alloy)
    current path meets the most
    stringent current carrying
    test, thus eliminating load
    capability concerns
    (76 K)

    Eliminate Load Capability Concerns
    The new RTE Rotatable Feedthru Inserts employ the time proven all copper alloy current path. (No aluminum current carrying components are used.) Unlike other feedthru devices, the mechanism that alls rotational positioning is not part of the primary current interchange. Therefore, mechanical wear from repeated installations will not degrade the current load capability of the device.

    The most stringent current carrying test recognized in the industry today is the current cycling test, the "Accelerated Thermal Test", defined in the latest draft of ANSI/IEEE 386. Our feedthru inserts have successfully passed this test, and thus eliminate load capability worries.


    Typical Applications

    The rotatable feedthru insert makes converting a radial feed to a loop feed transformer easy. (38 K) The rotatable feedthru insert makes adding an RTE M.O.V.E. arrester for overvoltage protection practical. (41 K)