home | about Cooper Power Systems | C3 - Cooper Customer Center | Cooper Industries | contact us

Switches

Three-Phase General Purpose Switches
VR, VLR, and VRV

The Kyle® Types VR, VLR, or VRV motor-operated oil switches provide convenient three-phase general purpose (Types VR and VRV) and inductive load (Type VLR) remote control switching. The motor-operated actuator enables the switch to be remotely controlled with a manually operated SPDT switch or by other control means. These economical, general purpose switches have a proven history of excellent performance servicing the utility industry for over thirty years. Reliable and dependable for various switching applications, these general purpose switches are the obvious choice.

Type VR and VLR switches are applicable to 14.4 kV applications. The Type VRV switch is applicable to 34.5 kV applications.

Type VR and VLR switches are differentiated from each other by their contact structures. Type VR switches have two sets of arcing and load-carrying contacts per phase. The Type VLR switch utilizes two bayonet-type moving contacts per phase operating within self-blast interrupters. This same type of contact structure is also used in the Type VRV switch with increased arc gaps for 34.5 kV applications.

A six-pin plug and receptacle are furnished for connecting the control circuits to the switch. Other standard equipment includes a contact-position indicator, an operations counter, a manual trip ring, and provision for manual closing. Accessories include a quick close feature, a manual trip and block switch, a four stage auxiliary switch, an operator cabinet heater, and low-voltage surge arresters for the externally connected control circuits.

Electrical Ratings

Description Types VR, VLR Type VRV
Rated maximum voltage (kV rms) 15.5 38.0
Nomial system voltage (kV rms) 2.4-14.4 34.5
Rated impulse voltage (BIL) (kV crest) 110 150
60 HZ insulation level withstand (kV rms)

   Dry, 1 minute

   Wet, 10 seconds



50

45


45

60
Rated Continuous current (amps) 400 400


Short-Time Current Ratings

Description Types VR, VLR Type VRV
Rated momentary asymmetrical current (amps) 20,000 15,000
Rated 1/2 second asymmetrical current (amps) 13,500
Rated 1 second symmetrical current (amps) 10,000 10,000
Rated 10 second symmetrical current (amps) 3,500
Rated asymmetrical making current 20,000 15,000


Load Switching Ratings

Type Application Power Factor (%) Rated Current (amp)
VR Capacitive current switching


Inductive load switching





75-100
50-75
10-50
300


@7.2 kV     @14.4kV
400200
200100
10050
VLR Inductive load switching 10-100 400
VRV Inductive load switching 70 400